SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
242
System Manual, 01/2011, A8E56203870002-03
2.8.1.6
Conductor cross-sections - 3RT201. contactors
Table 2- 83 Conductor cross-sections - 3RT201. contactors
Type
3RT2015
3RT2016
3RT2017
3RT2018
Size
S00
Conductor cross-sections
Main and auxiliary conductors
Screw connection
Solid + stranded
mm
2
2 x (0.5 to 1.5)
1)
; 2 x (0.75 to 2.5)
1)
acc. to IEC 60947;
max. 2 x 4
Finely stranded with end
sleeve
mm
2
2 x (0.5 to 1.5)
1)
; 2 x (0.75 to 2.5)
1)
Solid or stranded, AWG cables AWG
2 x (20 to 16)
1)
; 2 x (18 to 14)
1)
; 2 x 12
Connection screw
M3
(1 or 2
conductors
can be
connected)
for
standard
screwdriver
s size 2
and
Pozidriv 2
- Tightening torque
Nm
0.8 to 1.2 (7 to 10.3 lb.in)
Spring-loaded connection
Main and auxiliary conductors
Auxiliary conductor
Main conductor
Solid + stranded
mm
2
2 x (0.5 to 4)
2 x (0.5 to 4)
Finely stranded with end
sleeve
mm
2
2 x (0.5 to 2.5)
2 x (0.5 to 2.5)
Finely stranded without end
sleeve
mm
2
2 x (0.5 to 2.5)
2 x (0.5 to 2.5)
(1-wire or
2-wire
connection
possible)
AWG cables, solid or stranded AWG
2 x (20 to 12)
2 x (20 to 12)
Main and auxiliary conductors
Ring cable lug connection
Connection screw
M3 (Pozidriv size PZ 2)
Operating tool
mm
∅ 5 … 6
Tightening torque
Nm
0.8 to 1.2
mm
d
2
= min. 3.2
Usable ring cable lugs
mm
d
3
= max. 7.5
- DIN 46237 with insulating sleeve
- JIS C2805 type RAV with
insulating sleeve
- JIS C2805 type RAP with
insulating sleeve
- DIN 46234 without insulating
sleeve
- DIN 46225 without insulating
sleeve
- JIS C2805 type R without
insulating sleeve
PP
≥
1)
A shrink-on sleeve must be used to provide additional
insulation for the ring cable lugs
1)
.
Application temperature: -55 °C/+155 °C
UL 224 approved
Flame-protected
1)
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
located in the range indicated. If identical cross-sections are used, this restriction does not apply.