SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
234
System Manual, 01/2011, A8E56203870002-03
2.8.1.4
Actuation - 3RT201. contactors
Table 2- 80 Actuation - 3RT201. contactors
Type
3RT2015...16
3RT2017...18
Size
S00
Actuation
Magnet coil operating range
AC operation
50 Hz
0.8 to 1.1 x U
S
60 Hz
0.85 to 1.1 x U
S
DC operation
To 50 °C
0.8 to 1.1 x U
S
To 60 °C
0.85 to 1.1 x U
S
Magnet coil power input (for cold coil and 1.0 x Us)
AC operation, 50/60 Hz
Standard version
- Switch-on power
VA
27 / 24.3
37 / 33
- cos ϕ
0.8 / 0.75
- Holding power
VA
4.2 / 3.3
5.7 / 4.4
- cos ϕ
0.25 / 0.25
AC operation, 50 Hz, USA/Canada
- Switch-on power
VA
26.4
36
- cos ϕ at switch-on power
0.81
0.8
- Holding power
VA
4.4
5.9
- cos ϕ at holding power
0.24
AC operation, 60 Hz, USA/Canada
- Switch-on power
VA
31.7
43
- cos ϕ at switch-on power
0.81
0.8
- Holding power
VA
4.8
6.5
- cos ϕ at holding power
0.25
DC operation
- Switch-on power = holding power
W
4
Permissible residual current of electronics (with 0 signal)
AC operation
mA
< 3 mA x (239 V/U
S
);
the use of the
additional load module
3RT2916-1GA00 is
recommended at
higher residual
currents.
< 4 mA x (239 V/U
S
);
the use of the
additional load module
3RT2916-1GA00 is
recommended at
higher residual
currents.
DC operation
mA
< 10 mA x (24 V/U
S
); the use of the additional
load module 3RT2916-1GA00 is recommended
at higher residual currents.