Conductor cross-sections - 3RH2. contactor relays
Table 2- 116 Conductor cross-sections - 3RH2. contactor relays
Type
3RH21, 3RH22
3RH24
Size
S00
S00
Conductor cross-sections (1-wire or 2-wire connection possible)
Auxiliary conductor connections and coil terminals
Screw connection
Solid + stranded
mm
2
2 x (0.5 to 1.5); 2 x (0.75 to 2.5) acc. to IEC 60947;
max. 2 x 4
Finely stranded with end sleeve
mm
2
2 x (0.5 to 1.5); 2 x (0.75 to 2.5)
AWG cables, solid or stranded
AWG 2 x (20 to 16); 2 x (18 to 14); 2 x 12
Connection screws
M3
- Tightening torque
Nm
(lb.in.)
0.8 to 1.2 (7 to 10.3 lb.in.)
Auxiliary conductor connections and coil terminals (basic device)
Spring-loaded connection
Solid + stranded
mm
2
2 x (0.5 to 4)
Finely stranded with end sleeve
mm
2
2 x (0.5 to 2.5)
Finely stranded without end sleeve
mm
2
2 x (0.5 to 2.5)
AWG cables, solid or stranded
AWG 2 x (20 to 12)
Auxiliary conductor connections for auxiliary switch block mounted
on the front
Solid
mm
2
2 x (0.5 to 2.5)
Finely stranded with end sleeve
mm
2
2 x (0.5 to 1.5)
Finely stranded without end sleeve
mm
2
2 x (0.5 to 1.5)
AWG cables, solid or stranded
AWG 2 x (20 to 14)
Auxiliary conductor connections and coil terminals
Ring cable lug connection
Connection screw
M3 (Pozidriv size PZ 2)
Operating tool
mm
∅ 5 … 6
Tightening torque
Nm
0.8 to 1.2
mm
d
2
= min. 3.2
Usable ring cable lugs
mm
d
3
= max. 7.5
- DIN 46237 with insulating sleeve
- JIS C2805 type RAV with insulating sleeve
- JIS C2805 type RAP with insulating sleeve
- DIN 46234 without insulating sleeve
- DIN 46225 without insulating sleeve
- JIS C2805 type R without insulating sleeve
PP
≥
1)
A shrink-on sleeve must be used to provide
additional insulation for the ring cable lugs
1)
.
Application temperature: -55 °C/+155 °C
UL 224 approved