![Siemens SIRIUS 3RH Series System Manual Download Page 238](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139238.webp)
SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
238
System Manual, 01/2011, A8E56203870002-03
Type
3RT2015
3RT2016
3RT2017
3RT2018
Size
S00
Main circuit - Current carrying capacity for alternating current
Switching of gas discharge lamps with correction
Per main current path at 230 V
Shunt compensation with inductive ballast, rated power per
lamp/capacitance/rated operational current per lamp
L 18 W/4.5 μF/0.11 A
Qty.
17
22
29
39
L 36 W/4.5 μF/0.21 A
Qty.
15
19
21
L 58 W/7.0 μF/0.32 A
Qty.
10
14
L 80 W/7.0 μF/0.49 A
Qty.
6
9
With solid-state ballast
4)
single-lamp
L 18 W/6.8 μF/0.10 A
Qty.
49
63
84
112
L 36 W/6.8 μF/0.18 A
Qty.
27
35
46
62
L 58 W/10 μF/0.29 A
Qty.
16
21
28
38
L 80 W/10 μF/0.43 A
Qty.
11
14
19
26
With solid-state ballast
4)
two-lamp
L 18 W/10 μF/0.18 A
Qty.
27 (≙ 2 x 27
lamps)
35 (≙ 2 x 35
lamps)
46 (≙ 2 x 46
lamps)
62
(≙ 2 x 62
lamps)
L 36 W/10 μF/0.35 A
Qty.
14 (≙ 2 x 14
lamps)
18 (≙ 2 x 18
lamps)
24 (≙ 2 x 24
lamps)
32
(≙ 2 x 32
lamps)
L 58 W/22 μF/0.52 A
Qty.
9 (≙ 2 x 9
lamps)
12 (≙ 2 x 12
lamps)
16 (≙ 2 x 16
lamps)
21
(≙ 2 x 21
lamps)
L 80 W/22 μF/0.86 A
Qty.
5 (≙ 2 x 5
lamps)
7 (≙ 2 x 7
lamps)
9 (≙ 2 x 9
lamps)
13
(≙ 2 x 13
lamps)
Utilization category AC-5b, switching incandescent lamps
Per main current path at 230/220 V
kW
1.3
1.7
2.2
3
Summary of Contents for SIRIUS 3RH Series