Short-circuit protection
3.5.3.1
Mounting accessories for the load feeder conforming to IEC
3RF34 solid-state contactors - coordination 1 and 2 conforming to IEC
Combining 3RF34 solid-state contactors, type of coordination 1 (type 1), with 3RB3 overload relays
3RF34 solid-state contactors can be combined with the following 3RB3 overload relays in
conformance with type of coordination 1 (type 1):
Table 3- 6
Order designations for 3RB3 overload relays
3RF3 solid-state contactors
3RF3405-xBByz 5.2 A
3RF3410-xBByz 9.2 A
3RF3412-xBByz 12.5 A
3RF3416-xBByz 16 A
Compatible 3RB3 overload relays
3RB3.2.-N.. 0.32 - 1.25 A
3RB3.2.-N.. 0.32 - 1.25 A
3RB3.2.-N.. 0.32 - 1.25 A
3RB3.2.-N.. 0.32 - 1.25 A
3RB3.2.-P.. 1 - 4 A
3RB3.2.-P.. 1 - 4 A
3RB3.2.-P.. 1 - 4 A
3RB3.2.-P.. 1 - 4 A
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
–
3RB3.2.-Q.. 6 - 25 A
3RB3.2.-Q.. 6 - 25 A
3RB3.2.-Q.. 6 - 25 A
Combining 3RF34 solid-state contactors, type of coordination 2 (type 2), with 3RB3 overload relays
3RF34 solid-state contactors can be combined with the following 3RB3 overload relays in
conformance with type of coordination 2 (type 2):
Table 3- 7
Order designations for 3RB3 overload relays
3RF3 solid-state contactors
3RF3405-xBByz 5.2 A
3RF3410-xBByz 9.2 A
3RF3412-xBByz 12.5 A
3RF3416-xBByz 16 A
Compatible 3RB3 overload relays
3RB3.2.-N.. 0.32 - 1.25 A
(3RB3 determining fuse
protection)
3RB3.2.-N.. 0.32 - 1.25 A
(3RB3 determining fuse
protection)
3RB3.2.-N.. 0.32 - 1.25 A
(3RB3 determining fuse
protection)
3RB3.2.-N.. 0.32 - 1.25 A
(3RB3 determining fuse
protection)
3RB3.2.-P.. 1 - 4 A
3RB3.2.-P.. 1 - 4 A
3RB3.2.-P.. 1 - 4 A
(3RB3 determining fuse
protection)
3RB3.2.-P.. 1 - 4 A
(3RB3 determining fuse
protection)
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
3RB3.2.-S.. 3 - 12 A
–
3RB3.2.-Q.. 6 - 25 A
3RB3.2.-Q.. 6 - 25 A
3RB3.2.-Q.. 6 - 25 A
Table 3- 8
Supplements to order numbers:
x = type of connection system
1 = screw connection
2 = spring-loaded terminals
y = type of control voltage
0 = 24 V DC acc. to EN 61131-2
2 = 110 to 230 AC
z = type of rated control voltage
4 = 48 to 480 V
6 = 48 to 600 V