SIRIUS 3RR2 current monitoring relays
8.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
747
8.10.3.3
Conductor cross-sections main circuit
Table 8- 25 Technical data for the main circuit connection, 3RR22 current monitoring relays
Type
3RR2241
3RR2242
Size
S00
S0
Width
45 mm
45 mm
Connection type
Screw connection
Connection screw
M3, Pozidriv size 2
M4, Pozidriv size 2
Operating tool
∅ 5 to 6
∅ 5 to 6
Tightening torque
Nm
0.8 to 1.2
2 to 2.5
Conductor cross-sections (min./max.), 1-wire or 2-wire
- Solid
mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
1)
2 x (1 to 4)
1)
2 x (1 to 2.5)
1)
2 x (2.5 to 10)
1)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
2)
2 x (1 to 2.5)
1)
2 x (2.5 to 6)
1)
max. 1 x 10
- AWG cables, solid or stranded
AWG
2 x (20 to 14)
1)
1 x 12
1)
2 x (16 to 12)
1)
2 x (14 to 8)
1)
Connection type
Spring-loaded connection
Operating tool
∅ 3.0 x 0.5
Conductor cross-sections (min./max.)
- Solid
mm
2
1 x (0.5 to 4)
1 x (1 to 10)
- Finely stranded without end sleeve mm
2
1 x (0.5 to 2.5)
1 x (1 to 6)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
1 x (0.5 to 2.5)
1 x (1 to 6)
- AWG cables, solid or stranded
AWG
1 x (20 to 12)
1 x (18 to 8)
1)
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
located in the range indicated. If identical cross-sections are used, this restriction does not apply.