![Siemens SIRIUS 3RH Series System Manual Download Page 738](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139738.webp)
SIRIUS 3RR2 current monitoring relays
8.10 Technical data
SIRIUS Innovations
738
System Manual, 01/2011, A8E56203870002-03
8.10.2
3RR21 Basic analog setting current monitoring relay
8.10.2.1
General technical data
Table 8- 18 General technical data for 3RR21 current monitoring relays
Type
3RR2141
3RR2142
Size
S00
S0
Width
45 mm
45 mm
Tripping in the event of
Overcurrent, undercurrent, phase failure
Phase loss sensitivity
Yes
Number of phases
2
Number of monitored phases
2
Overload warning
No
Resetting and recovery
Reset options following tripping
Manual and automatic reset
Recovery time following error
- Automatic RESET
s
0.3
- Manual RESET
s
0.3
Adjustable ON-delay time
On startup
s
0 ... 60
On upper or lower limit violation
s
0 ... 30
Maximum response time
ms
300
Relative switching hysteresis
%
6.25
Relative repeat accuracy
%
2
Ambient temperature
Storage/transport
°C
-40 ... + 80
Operation
°C
-25 ... + 60
Resistance to extreme climates - Humidity
%
Condensation not permissible
Repeat terminals
Coil repeat terminal
Yes
Not required
Auxiliary switch repeat terminal
Yes
Not required
Degree of protection acc. to IEC 60529
IP20
Touch protection acc. to IEC 61140
Finger-safe
Shock resistance with sine
acc. to IEC 60068-2-27
g/ms
15 / 11
Vibration resistance
Hz
10 to 55 per 0.35 mm
Summary of Contents for SIRIUS 3RH Series
Page 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Page 2: ......
Page 785: ......