General data - Mechanical latch 3RT2926-3A
Table 2- 122 General data 3RT2926-3A
Contactor
Type
3RT2926-3A
Size
Mechanical latch for 3RT2.2 contactors
General data
Rated insulation voltage U
i
(pollution degree 3)
V
690
Mechanical durability
(operating cycles)
With 3RT2.2
Operati
ng
cycles
3 million
Permissible ambient temperature
Operation
°C
-25 … + 60
Storage
°C
-50 … + 80
Degree of protection to EN 60947-1, Annex C
IP20
Magnet coil operating range
at AC 50/60 Hz and DC
0.85 to 1.1 x U
S
Release solenoid magnet coil power input (for cold
coil and 1.0 x U
S
)
AC and DC operation
W
Approx. 4
Command duration for de-energizing
AC operation
ms
18 ... 31
DC operation
ms
18 ... 26
Conductor cross-sections
mm2
2 x (0.5 to 2.5); 1 x 4
Solid
AWG
2 x 14; 1 x 12
mm2
2 x (0.5 to 2.5); 1 x 2.5
Finely stranded with end sleeve
AWG
2 x 14; 1 x 12
Nm
0.8 to 1.1
Tightening torque of connection screws
lb.in
7 to 9.5