Table 8- 10 Disassembling the terminal support (screw-type connection system)
Step
Operating instruction
Figure
1
Undo the screws on the main conductor terminals.
2
Release the current monitoring relay by pushing down
the clip on the underside of the terminal support.
3
Use a screwdriver to dislodge the terminal support
from the current monitoring relay.
4
Pull the current monitoring relay down and away from
the contactor.
Table 8- 11 Disassembling the terminal support (spring-loaded connection system)
Step
Operating instruction
Figure
1
Release the current monitoring relay by pushing down
the clip on the underside of the terminal support.
2
Position the screwdriver on the terminal support as
shown in the figure. Carefully dislodge the current
monitoring relay from the contactor.
3
Pull the current monitoring relay toward you and away
from the terminal support.