Advanced commissioning
6.11 Safe Torque Off (STO) safety function
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
159
You have set the forced checking procedure (test stop) for the Basic Functions.
❒
Description
The forced checking procedure (test stop) of the basic functions is an inverter self test. The
inverter checks its circuits to switch off the torque. If you are using the Safe Brake Relay, for
a forced checking procedure, the inverter also checks the circuits of this component.
You start the forced checking procedure each time that the STO function is selected.
Using a timer block, the inverter monitors as to whether the forced checking procedure is
regularly performed.
Figure 6-23 Starting and monitoring the forced checking procedure (test stop)
Parameter
Description
p9659
Forced dormant error detection timer (Factory setting: 8 h)
Monitoring time for the forced dormant error detection.
r9660
Forced dormant error detection remaining time
Displays the remaining time until the forced dormant error detection and testing the
safety switch-off signal paths.
r9773.31
1 signal: Forced dormant error detection is required
Signals for the higher-level control system.
Activate settings
Requirement
You are online with Startdrive.