Advanced commissioning
6.5 Jogging
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
133
Jog settings
Parameter
Description
p1058
Jogging 1 speed setpoint (factory setting 150 rpm)
p1059
Jogging 2 speed setpoint (factory setting -150 rpm)
p1082
Maximum speed (factory setting 1500 rpm)
p1110
Inhibit negative direction
=0: Negative direction of rotation is enabled =1: Negative direction of rotation is
inhibited
p1111
Inhibit positive direction
=0: Positive direction of rotation is enabled =1: Positive direction of rotation is
inhibited
p1113
Setpoint inversion
=0: Setpoint is not inverted
=1: Setpoint is inverted
p1120
Ramp-function generator ramp-up time (factory setting 10 s)
p1121
Ramp-function generator ramp-down time (factory setting 10 s)
p1055 = 722.0 Jog bit 0: Select jogging 1 via digital input 0
p1056 = 722.1 Jog bit 1: Select jogging 2 via digital input 1