Installation
4.1 Mechanical Installation
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
35
Mounting orientation
Mount the converter on a table or on a wall. The minimum clearance distances are as
follows:
●
Side-by-side - no clearance distance is required
●
Above and below the inverter 150 mm (5.9 inches).
Figure 4-3
Mounting orientation: correct (
✓
), impermissible (X), permissible with restrictions (!)
Restrictions due to vertical mounting
If the converter is mounted in the vertical position, the maximum ambient temperature is
40°C.
Additionally you have to reduce the converter output current to 80 % of rated converter
current.
If the output current derating adversely affects the application, you have to use an converter
of the next highest power rating.