Installation
4.4 Connecting the inverter to PROFIBUS
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
79
If you are working with Startdrive, back up the settings so they are not lost if the power
fails.
Overview of the interfaces (Page 36)
Setting the bus address
Procedure
1.
Set the address using one of the subsequently listed options:
–
Via the address switch
–
On an operator panel via p0918
–
With Startdrive
Confirm the prompt for saving your settings (copy RAM to ROM).
2.
Switch off the inverter power supply.
3.
Wait until all LEDs on the inverter are dark.
4.
Switch on the inverter power supply again.
Your settings become effective after switching on.
The PROFIBUS address is set.
❒