Advanced commissioning
6.4 Drive control via PROFIBUS or PROFINET
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
119
Bit Significance
Remarks
Signal inter-
connection
in the in-
verter
Telegram 20
All other tele-
grams
7
1 = Alarm active
Motor remains switched on; no acknowl-
edgement is necessary.
p2080[7] =
r2139.7
8
1 = Speed deviation within the
tolerance range
Setpoint / actual value deviation within the
tolerance range.
p2080[8] =
r2197.7
9
1 = Master control requested
The automation system is requested to ac-
cept the inverter control.
p2080[9] =
r0899.9
10 1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corre-
sponding maximum speed.
p2080[10] =
r2199.1
11 1 = current or
torque limit
reached
1 = torque limit
reached
Comparison value for current or torque has
been reached or exceeded.
p2080[11] =
r0056.13 /
r1407.7
12 ---
1)
1 = Holding
brake open
Signal to open and close a motor holding
brake.
p2080[12] =
r0899.12
13 0 = Alarm, motor overtemperature --
p2080[13] =
r2135.14
14 1 = Motor rotates clockwise
Internal inverter actual value > 0
p2080[14] =
r2197.3
0 = Motor rotates counter-
clockwise
Internal inverter actual value < 0
15 1 = CDS display 0 = Alarm, in-
verter thermal
overload
p2080[15] =
r0836.0 /
r2135.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous
telegram is kept.