Advanced commissioning
6.12 Setpoints
Converter with the control units CU240D-2
174
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Parameter
Parameter
Description
Setting
p1001[0...n]
Fixed speed setpoint 1 [rpm] Fixed speed setpoint 1
Factory setting: 0 rpm
p1002[0...n]
Fixed speed setpoint 2 [rpm] Fixed speed setpoint 2
Factory setting: 0 rpm
...
...
...
p1015[0...n]
Fixed speed setpoint 15
[rpm]
Fixed speed setpoint 15
Factory setting: 0 rpm
p1016
Fixed speed setpoint mode
Fixed speed setpoint mode
Factory setting: 1
1: Direct
2: Binary
p1020[0...n]
Fixed speed setpoint selec-
tion, bit 0
Fixed speed setpoint selection, bit 0
Factory setting: 0
p1021[0...n]
Fixed speed setpoint selec-
tion, bit 1
Fixed speed setpoint selection, bit 1
Factory setting: 0
p1022[0...n]
Fixed speed setpoint selec-
tion, bit 2
Fixed speed setpoint selection, bit 2
Factory setting: 0
p1023[0...n]
Fixed speed setpoint selec-
tion, bit 3
Fixed speed setpoint selection, bit 3
Factory setting: 0
r1024
Fixed speed setpoint active
Fixed speed setpoint active
r1025.0
Fixed speed setpoint status Fixed speed setpoint status
1 signal: Fixed speed setpoint is selected
Further information
Additional information about binary selection can be found in function diagram 3010 in the
List Manual.
Additional information about direct selection can be found in function diagram 3011 in the
List Manual.
Application example: Directly selecting two fixed speed setpoints
The motor should operate at different speeds as follows:
●
The signal on digital input 0 switches the motor on and accelerates it to 300 rpm.
●
The signal at digital input 1 accelerates the motor to 2000 rpm.
●
The signals at the two digital inputs accelerate the motor to 2300 rpm.