Backing up data and series commissioning
7.4 Other ways to back up settings
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
253
7.4
Other ways to back up settings
In addition to the default setting, the inverter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
Additional information is available on the Internet: Memory options
http://support.automation.siemens.com/WW/view/en/43512514
7.5
Write protection
The write protection prevents unauthorized changing of the inverter settings. If you are
working with a PC tool, such as STARTER, then write protection is only effective online. The
offline project is not write-protected.
Write protection is applicable for all user interfaces:
●
Operator Panel BOP-2 and IOP-2
●
STARTER or Startdrive PC tool
●
Parameter changes via fieldbus
No password is required for write protection.
Activate and deactivate write protection
Procedure with STARTER
1.
Go online.
2.
Open the shortcut menu of the required inverter.
3.
Activate or deactivate write protection.
4.
Press the "Copy RAM to ROM" button to retentively save the settings .