Installation
4.4 Connecting the inverter to PROFIBUS
Converter with the control units CU240D-2
76
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
4.3.3
Installing GSDML
Procedure
1.
Save the GSDML to your PC.
–
With Internet access:
GSDML
http://support.automation.siemens.com/WW/view/en/22339653/133100
–
Without Internet access:
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
2.
Unzip the GSDML file on your computer.
3.
Import the GSDML into the engineering system of the controller.
You have now installed the GSDML in the engineering system of the controller.
❒
4.4
Connecting the inverter to PROFIBUS
The PROFIBUS DP interface has the following functions:
●
Cyclic communication
●
Acyclic communication
●
Diagnostic alarms
General information on PROFIBUS DP can be found in the Internet:
●
PROFIBUS user organization (
http://www.profibus.com/downloads/installation-
●
Information about PROFIBUS DP (