Advanced commissioning
6.14 PID technology controller
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
187
Precondition
Additional functions
The motor closed-loop control is set
Tools
To change the function settings, you can use an operator panel or a PC tool, for example.
Function description
Function diagram
The technology controller is implemented as a PID controller (controller with proportional,
integral, and derivative action).
①
The inverter uses the start value when all the following conditions are simultaneously satisfied:
•
The technology controller supplies the main setpoint (p2251 = 0).
•
The ramp-function generator output of the technology controller has not yet reached the start value.
Figure 6-35 Simplified representation of the technology controller
Basic settings
The settings required as a minimum are marked in gray in the function diagram:
●
Interconnect setpoint and actual values with signals of your choice
●
Set ramp-function generator and controller parameters K
P
, T
I
and T
d
.