Advanced commissioning
6.4 Drive control via PROFIBUS or PROFINET
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
121
Status word 3 (ZSW3)
Bit Meaning
Description
Signal intercon-
nection in the
inverter
0
1 = DC braking active
--
p2051[3] = r0053
1
1 = |n_act | > p1226
Absolute current speed > stationary
state detection
2
1 = |n_act | > p1080
Absolute actual speed > minimum
speed
3
1 = i_act
≧ p2170
Actual current ≥ current threshold
value
4
1 = |n_act | > p2155
Absolute actual speed > speed
threshold value 2
5
1 =
|n_act | ≦ p2155
Absolute actual speed < speed
threshold value 2
6
1 =
|n_act | ≧ r1119
Speed setpoint reached
7
1 = DC li
nk voltage ≦ p2172
Actual DC link voltage ≦ threshold
value
8
1 = DC link voltage > p2172
Actual DC link voltage > threshold
value
9
1 = ramp-up or ramp-down complet-
ed
Ramp-function generator is not
active.
10 1 = technology controller output at
the lower limit
Technology controller output ≦
p2292
11 1 = technology controller output at
the upper limit
Technology controller out-
put > p2291
12 Not used
13 Not used
14 Not used
15 Not used