Advanced commissioning
6.6 Limit position control
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
135
①
The motor moves the machine component in the direction of the positive limit position.
②
The positive limit position has been reached. The motor stops with the OFF3 ramp-down time.
③
The motor moves the machine component in the opposite direction at a 0
→
1 signal change.
④
The negative limit position has been reached. The motor stops with the OFF3 ramp-down time.
⑤
The motor moves the machine component in the opposite direction at a 0
→
1 signal change.
Figure 6-15 Limit position control of the inverter
Parameter
Explanation
p3340[0 … n]
Start limit switch
1 signal: Start is active
0 signal: Start is inactive
p3342[0 … n]
Minus limit switch
1 signal: Limit switch is inactive
0 signal: Limit switch is active
p3343[0 … n]
Plus limit switch
r3344
Limit switch ON/OFF
.00
1 signal: Limit switch ON
0 signal: Limit switch OFF1
.01
1 signal: Limit switch no OFF3
0 signal: Limit switch OFF3
.02
1 signal: Limit switch, axis stationary (standstill)
.04
1 signal: Plus limit switch actuated
.05
1 signal: Minus limit switch actuated
See also