Startup
7.3 Parameterizing the device
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
93
7.3.4.4
Setting the voltage input
The factory setting for the measuring reference voltage is 400 V. At initial startup, the
following steps must be carried out if the available measuring voltage deviates from this.
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
3.
Go to the "VOLTAGE INPUTS" device setting:
<F2>
or <F3>
Figure 7-7
"VOLTAGE INPUTS" device setting
4.
Open edit mode of the "VOLTAGE INPUTS" device setting:
<F4>
5.
Set the desired value:
<F2>
and <F3>
6.
Accept the value:
<F4>
The value of the voltage input is permanently saved and becomes effective immediately.
The display returns to display mode.
7.
Return to one of the selection menus or to the measured values display:
<F1>