Service and maintenance
10.4 Replacing the battery
SENTRON PAC4200
148
Manual, 09/2008, A5E02316180B-01
Replacement battery
Use a replacement battery that meets the technical requirements. Please read the
instructions in the chapter "Technical specifications".
WARNING
Combustion or explosion of the battery
Can cause death, serious injury or considerable property damage.
The battery must meet the safety requirements of UL1642, to avoid combusion or
explosion.
Use only batteries tested in accordance with UL1642.
Tools
Use the following tool for replacing the battery:
●
Angled pointed pliers with insulated jaws.
Procedure
Follow the steps below to change the battery:
1.
Make sure that the replacement battery has the full charging capacity and is available on
site when commencing the work.
2.
Back up the device's data.
–
Go to the dialog "CHANGE BATTERY".
SETTINGS > ADVANCED > CHANGE BATTERY
Figure 10-1 "CHANGE BATTERY"
–
Select the "CHANGE BATTERY START" entry:
key <F4>
This will start data back-up. The SENTRON PAC4200 copies the data from the
battery-backed memory into the internal non-volatile memory. The data do not leave
the device.
The device indicates completion of data backup.
Figure 10-2 Indication of completed data backup
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...