Technical data
11.1 Technical data
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
157
Communication
Ethernet ports
Number
1
Type
RJ45 (8P8C)
Suitable cable types
100Base-TX (CAT5)
Grounding of cable required.
Protocols supported
MODBUS TCP
Transfer rates
10 / 100 Mbit/s, Autonegotiation and Auto-MDX
(Medium Dependent Interface)
Update time at the interface
200 ms for instantaneous values and energy
counters.
Sliding window demand values are updated up to
60 times during the configured averaging time,
e.g. once every second if the averaging time is
set to 60 seconds.
Serial gateway
Function
Serial gateway for converting MODBUS TCP to
MODBUS RTU or SEAbus
Requirements for use
SENTRON PAC RS485 expansion module
Number of devices that can be
operated
Max. 31 without repeaters
Max. 247 with repeaters
Port number
17002 if the SENTRON PAC RS485 expansion
module is operated at the "MOD1" slot
17003 if the SENTRON PAC RS485 expansion
module is operated at the "MOD2" slot
Displays and controls
Display
Type
Monochrome, graphics LC display
Backlit display
White, invertible display
Resolution
128 x 96 pixels
Size W x H
72 mm x 54 mm
Refresh time
0.33 ... 3 sec, adjustable
Keyboard
4 function keys F1 to F4 on the front
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...