Appendix
A.3 MODBUS
SENTRON PAC4200
210
Manual, 09/2008, A5E02316180B-01
Offset Number of
registers
Name
Format
Unit
Value range
Access
3103
6
Maximum Reactive Power c (VARn)
with Time
Float + time stamp VAR
-
R
3109
6
Maximum Total Reactive Power a
(VARtot) with Time
Float + time stamp VAR
-
R
3115
6
Maximum Total Reactive Power b
(VARtot) with Time
Float + time stamp VAR
-
R
3121
6
Maximum Total Reactive Power c
(VARtot) with Time
Float + time stamp VAR
-
R
3127
6
Maximum Reactive Power a (VAR1)
with Time
Float + time stamp VAR
-
R
3133
6
Maximum Reactive Power b (VAR1)
with Time
Float + time stamp VAR
-
R
3139
6
Maximum Reactive Power c (VAR1)
with Time
Float + time stamp VAR
-
R
3145
6
Maximum Power Factor a with Time Float + time stamp -
0 … 1
R
3151
6
Maximum Power Factor b with Time Float + time stamp -
0 … 1
R
3157
6
Maximum Power Factor c with Time
Float + time stamp -
0 … 1
R
3163
6
Maximum THD Voltage a-b referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3169
6
Maximum THD Voltage b-c referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3175
6
Maximum THD Voltage c-a referred
to Fundamental with Time
Float + time stamp %
0 ... 100
R
3199
6
Maximum cos φ a with Time
Float + time stamp cos φ
a
-
R
3205
6
Maximum cos φ b with Time
Float + time stamp cos φ
b
-
R
3211
6
Maximum cos φ c with Time
Float + time stamp cos φ
c
-
R
3217
6
Maximum Displacement Angle a with
Time
Float + time stamp φ
-
R
3223
6
Maximum Displacement Angle b with
Time
Float + time stamp φ
-
R
3229
6
Maximum Displacement Angle c with
Time
Float + time stamp φ
-
R
3253
6
Maximum THD Voltage a with Time
Float + time stamp %
0 ... 100
R
3259
6
Maximum THD Voltage b with Time
Float + time stamp %
0 ... 100
R
3265
6
Maximum THD Voltage c with Time
Float + time stamp %
0 ... 100
R
3271
6
Maximum THD Current a with Time
Float + time stamp %
0 ... 100
R
3277
6
Maximum THD Current b with Time
Float + time stamp %
0 ... 100
R
3283
6
Maximum THD Current c with Time
Float + time stamp %
0 ... 100
R
3289
6
Maximum Distortion a with Time
Float + time stamp A
-
R
3295
6
Maximum Distortion b with Time
Float + time stamp A
-
R
3301
6
Maximum Distortion c with Time
Float + time stamp A
-
R
3307
6
Maximum Line Frequency with Time Float + time stamp -
45 ... 65
R
3313
6
Maximum 3-Phase Average Voltage
ph-n with Time
Float + time stamp V
-
R
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...