Technical data
11.1 Technical data
SENTRON PAC4200
156
Manual, 09/2008, A5E02316180B-01
Digital inputs
Number
2 inputs
Input voltage
Rated value
24 V DC
Maximum input voltage
30 V DC (SELV or PELV supply)
Permissible signal level for signal
"0" detection
< 10 V DC
Permissible signal level for signal
"1" detection
> 19 V DC
Input current
For signal "1"
typ. 4 mA (24 V)
Max. input delay
Signal "0" to "1"
5 ms
Signal "1" to "0"
5 ms
Digital outputs
Number
2 outputs
Design/function
Switching output or pulse output
Operating voltage
12 to 24 V DC, max. 30 V DC (SELV or PELV
supply)
Output current
With "1" signal
Depends on the load and the external power
supply
Continuous load
Max. 100 mA
(thermal overload protection)
Transient overload
max. 300 mA for a duration of 100 ms
Resistive load
100 mA
With "0" signal
max. 0.2 mA
Internal resistance
55 Ω
Short-circuit protection
Yes
Overvoltage category
CAT I
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30 to 500 ms
Minimal settable time frame
10 ms
Switching function
Max. output delay
With signal "0" to "1"
5 ms
With signal "1" to "0"
5 ms
Max. switching frequency
17 Hz
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...