Description
3.9 Digital inputs and outputs
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
43
The output of pulses or edges can be parameterized.
The rising and falling edges are counted.
W
(
('*(
38/6(
Figure 3-15 Types of count signal
The digital output is passive and implemented exclusively as a switch.
The implementation of the pulse shape corresponds to the IEC 62053-31 standard.
Pulse length, turn-off time
(1)
Pulse length
(2)
Turn-off time
Figure 3-16 Pulse length and turn-off time
●
Pulse length:
Time for which the signal at the digital output is "high". The minimum pulse length is
30 ms and the maximum 500 ms.
●
Turn-off time:
Time for which the signal at the digital output is "low". The turn-off time depends on the
measured energy, for example, and can be days or months.
●
Minimum turn-off time:
The minimum turn-off time is specified by the programmed pulse length.
Digital Inputs
The following functions can be assigned to the digital inputs:
●
Tariff switching for on-peak and off-peak.
●
Synchronization of the measuring period by means of the synchronization pulse of a
system control center or other device.
●
Synchronization of the internal clock ("Top of minute").
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...