Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
137
LIMIT LOGIC
Logical truth value resulting from the combination of up to 12 limit values "LIM0" to "LIM11",
taking account of the logical priority rules and allowing logical brackets.
The logic is represented on the display using the graphic symbols familiar from digital
technology.
Value "true": A violation has occurred
Value "false": No violation has occurred
Figure 9-13 "LIMIT LOGIC" device settings
LIM0, LIM1, ..., LIM11
Limit values used to generate the logically combined limit
"LIMIT LOGIC".
A higher-level logic function block with four inputs
supplies the result of the logic operation "LIMIT
LOGIC".
Four logic function blocks, each with four inputs, are
connected to these four inputs.
Logic function block with four inputs. Supplies the
output value to the input of the higher-level logic
function block.
Each of the four inputs can be assigned:
•
One of the twelve limit values LIM0 to LIM11
•
One of the digital inputs I0.0 or I0.1
Logic operations
Six logic operations:
AND, OR, XOR and their negations NAND, NOR,
XNOR
AND
AND logic operation: The output value is only true if
all input values are true. The output value is false if
any one of the input values or several input values
are false.
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...