Technical data
11.1 Technical data
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
155
Power supply
Design of the power supply.
Wide-voltage power supply AC / DC
Rated range
95 … 240 V AC (50/60 Hz) or
110 … 340 V DC
Work area
± 10% of AC/DC rated range
Power consumption
Without expansion module
Typically 11 VA AC, 5.5 W DC
With 2 expansion modules
Max. 32 VA AC, max. 11 W DC
Overvoltage category
CAT III
Battery
Types
BR2032
CR2032
(not rechargeable)
Approved in accordance with UL1642
Nominal voltage
3 V
Nominal discharge current
0.2 mA
Minimum permissible reverse current to the
battery
5 mA
Ambient temperature
The battery must be designed for at least 70°C.
Service life
5 years under the following conditions:
2 months backup time per year at 23°C,
10 months continuous operation per year at the
maximum permissible ambient temperature
Retention of data and time of day in the absence of the supply voltage
The backup time after 5 years operation is approximately 2 months under the following
conditions: 2 months backup time per year at 23°C, 10 months continuous operation per
year at the maximum permissible ambient temperature.
Memory
The long-term memory is sufficient to save up to four measured variables and their extreme
values every 15 minutes for 40 days.
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...