Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
135
SOURCE
Monitored data source.
Almost all measured variables can be selected
as the source.
The short codes are assigned to the measured
variables in the Appendix, in the right column
"LIM SOURCE" of the table "MEASURED
VARIABLES".
Default value:
V a
MODE
Relational operators
GREATER THAN, LOWER THAN the value in
the "VALUE" field.
Default operator: GREATER THAN
VALUE
Monitored threshold.
PICKUP DELAY
Delay before reporting the limit violation in seconds.
The delay refers to the appearance of the limit
violation or the point of exceeding the threshold
defined in the "VALUE" field. See the figure below
"Effect of delay".
Range: 0 to 10 s
Default value: 0 s
HYSTERESIS
Threshold buffer, prolongs the limit violation.
The hysteresis refers to the disappearance of the limit
violation or the point when the level returns below the
defined threshold.
Range: 0.0 to 20.0 %
Default value: 0,0 %
The percentage refers to the threshold value in the
"VALUE" field. See the figure below "Effect of delay
and hysteresis".
STATUS
Indicates whether the limit value is currently violated.
Yes, violation.
No, no violation.
LIMIT LOGIC
Refer to the following section "LIMIT LOGIC"
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...