Appendix
A.3 MODBUS
SENTRON PAC4200
240
Manual, 09/2008, A5E02316180B-01
Offset Number of
registers
Name
Format
Applicable
MODBUS
function codes
Value range
Access
5 =
Reactive energy
import tariff 1
6 =
Reactive energy
import tariff 2
7 =
Reactive energy
export tariff 1
8 =
Reactive energy
export tariff 2
9 =
Apparent energy
tariff 1
10 = Apparent energy
tariff 2
60005
1
Synchronization of
demand period
Unsigned
short
0x06
1 ... 60 min
W
0 =
On-peak tariff
60006
1
Switching tariff
Unsigned
short
0x06
1 =
Off-peak tariff
W
60007
1
Acknowledge diagnostics
bits
Unsigned
short
0x06
0-ffffh
W
Byte 0 Bit 4
and Bit 7
Ports
0 ... 11
Byte 0
Bits 0 ... 3
Port bit
numbers
0 ... 7
Byte 1 = 0
Output port.
Port bit
number
OFF
60008
1
Switching outputs (if
parameterized)
Unsigned
short
0x06
Byte 1 = 1
Output port.
Port bit
number ON
W
Hi 0 ... 99, Lo 0 ... 1
HiByte Group
assignment
60009
1
Switching command for
vector group
Unsigned
short
0x06
LoByte 0 = ON
1 = OFF
W
60010
1
Reset operating hours
counter
Unsigned
short
0x06
-
W
60011
1
Reset load profile
recording
Unsigned
short
0x06
-
W
60012
1
Reset event recording
Unsigned
short
0x06
-
W
60013
1
Set standard event
recording conditions
Unsigned
short
0x06
-
W
60014
1
Set standard I/O
parameters
Unsigned
short
0x06
-
W
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...