Description
3.16 Events
SENTRON PAC4200
52
Manual, 09/2008, A5E02316180B-01
Table 3- 6
The following events are reported:
Event
Event
class
Standard
warning
level
Reason
Remedy
START PMD
System
information
Information Voltage recovery
-
PMD INFO
System
information
Warning
PMD information
Please contact Support.
COMM.FAULT
System
information
Warning
A communications fault has
occurred at the slot xx interface.
Check the network
settings
FW UPDATE #
System
information
Warning
Transmission error:
The firmware is not suitable.
Make sure you are using
the correct firmware
version for the update.
Restart the firmware
update.
TIME CORR:
System
information
Information Top of minute:
The time has been corrected.
-
TIME SYNC #
System
information
Information The time synchronization has
failed.
Interface: Slot xx
The "Top of minute"
pulses for synchronizing
the time are not active.
Check the hardware and
the settings for
transmitting the "Top of
minute" pulses.
VOLTAGE #
Operating
information
Warning
The supply voltage has been
interrupted.
Measured variable x
The device has been
disconnected from the
network in accordance
with the schedule.
An error has occurred.
Check the power supply.
VOLTAGE
Operating
information
Alarm
The voltage is out of range
Measured variable x
CURRENT
Operating
information
Alarm
The current is out of range.
Measured variable x
Danger of serious or
fatal injury or of serious
damage to the device.
Make sure the system is
operating under
conditions for which
SENTRON PAC is
approved.
It is possible that the
measurements are not
correctly displayed.
Please contact Support.
LIMIT
Operating
information
Information The upper limit value xxxx has
been exceeded.
Measured variable x, limit
value xxxx
-
LIMIT
Operating
information
Information The lower limit value xxxx has
been exceeded.
Measured variable x, limit
value xxxx
-
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...