Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
211
Offset Number of
registers
Name
Format
Unit
Value range
Access
3319
6
Maximum 3-Phase Average Voltage
ph-ph with Time
Float + time stamp V
-
R
3325
6
Maximum 3-Phase Average Current
with Time
Float + time stamp A
-
R
3331
6
Maximum Total Apparent Power with
Time
Float + time stamp VA
-
R
3337
6
Maximum Total Active Power with
Time
Float + time stamp W
-
R
3343
6
Maximum Total Reactive Power
(VARn) with Time
Float + time stamp VAR
-
R
3349
6
Maximum Total Power Factor with
Time
Float + time stamp -
-
R
3355
6
Maximum Neutral Current with Time Float + time stamp A
-
R
3361
6
Maximum Total Reactive Power
(VARtot) with Time
Float + time stamp VAR
-
R
3367
6
Maximum Total Reactive Power
(VAR1) with Time
Float + time stamp VAR
-
R
3373
6
Max. Sliding Window Demand
Voltage a-n with Time
Float + time stamp V
-
R
3379
6
Max. Sliding Window Demand
Voltage b-n with Time
Float + time stamp V
-
R
3385
6
Max. Sliding Window Demand
Voltage c-n with Time
Float + time stamp V
-
R
3391
6
Max. Sliding Window Demand
Voltage a-b with Time
Float + time stamp V
-
R
3397
6
Max. Sliding Window Demand
Voltage b-c with Time
Float + time stamp V
-
R
3403
6
Max. Sliding Window Demand
Voltage c-a with Time
Float + time stamp V
-
R
3409
6
Max. Sliding Window Demand
Current a with Time
Float + time stamp A
-
R
3415
6
Max. Sliding Window Demand
Current b with Time
Float + time stamp A
-
R
3421
6
Max. Sliding Window Demand
Current c with Time
Float + time stamp A
-
R
3427
6
Max. Sliding Window Demand
Apparent Power a with Time
Float + time stamp VA
-
R
3433
6
Max. Sliding Window Demand
Apparent Power b with Time
Float + time stamp VA
-
R
3439
6
Max. Sliding Window Demand
Apparent Power c with Time
Float + time stamp VA
-
R
3445
6
Max. Sliding Window Demand Active
Power a with Time
Float + time stamp W
-
R
3451
6
Max. Sliding Window Demand Active
Power b with Time
Float + time stamp W
-
R
3457
6
Max. Sliding Window Demand Active
Power c with Time
Float + time stamp W
-
R
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...