Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
123
Use PTs?
Measurement with/without voltage transformer
ON/OFF switch: ON / OFF.
ON: Measurement using voltage transformers.
When measuring via voltage transformer, the device
must know the voltage conversion ratio. For this
purpose, the primary and secondary voltages must be
specified in the fields "PT PRIMARY" and "PT
SECONDARY".
When changing from direct measurement to
measurement using voltage transformers, the device
accepts the last set reference measuring voltage as the
secondary voltage and as the primary voltage.
OFF: Measurement direct on the low-voltage
system.
When changing from measurement using voltage
transformers to direct measurement, the device
accepts the last set secondary voltage as the reference
measuring voltage.
Default: Off
VOLTAGE INPUT
Rated voltage of the measuring system. Must be specified if
measuring is done direct on the system without voltage
transformers.
Range: 1 V to 690 V, freely adjustable (max. 600 V for
Vph)
Default value: 400 V
The property "VOLTAGE INPUT" is only visible, if
"USE PTs?" is set to " Off".
PT PRIMARY
Primary voltage. Must be specified if a voltage transformer is
used for measuring.
Range: 1 V to 999999 V, freely adjustable
Default value: 400 V
The property "PT PRIMARY" is only visible, if
"USE PTs?" is set to " On".
PT SECONDARY
Secondary voltage. Must be specified if a voltage transformer
is used for measuring.
Range: 1 V to 690 V, freely adjustable (max. 600 V for
Vph)
Default value: 400 V
The property "PT SECONDARY" is only visible, if
"USE PTs?" is set to " ON".
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...