Application planning
6.5 Use in IT networks
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
73
If the above-listed requirements cannot be met by the customer, the values of the table
below apply:
Table 6- 4
I
cu
values depending on V
e
in the event of a fault
V
e
3VL1
3VL2
3VL3
3VL4
3VL5
3VL6
3VL7
3VL8
I
IT
at 240 V
3 kA
3 kA
3,5 kA
4,8 kA
8,7 kA
9,6 kA
15 kA
--
I
IT
at 415 V
3 kA
3 kA
3,5 kA
4,8 kA
8,7 kA
9,6 kA
15 kA
--
I
IT
at 690 V
3 kA
3 kA
3,5 kA
4,8 kA
8,7 kA
9,6 kA
15 kA
--