Technical data
12.8 Motorized operating mechanisms
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
171
12.8
Motorized operating mechanisms
The following specifications apply for the motorized operating mechanism with and without stored
energy (model-dependent and size-dependent) for the SENTRON VL circuit breaker:
Table 12- 35 Stored-energy motorized operating mechanism for VL160x, VL160 to VL400 or without stored energy for
VL160X, VL160 and VL250 (deviating values in brackets)
Type
VL160X
VL160
VL250
VL400
Synchronizable
X
X
X
X
Operating range
[V]
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
Minimum command duration at V
S
[ms]
50
50
50
50
Max. command duration
1)
[ms]
Jog/pushbutton or continuous command
Total closing time
[ms]
<100 (3000)
<100 (3000)
<100 (3000)
<100
Break time
[s]
<5 (3)
<5 (3)
<5 (3)
<5
Pause between ON and OFF command
[s]
>1 (3)
>1 (3)
>1 (3)
>1
Pause between OFF and ON command
[s]
>5 (3)
>5 (3)
>5 (3)
>5
Max. permissible switching frequency
1/h
120
120
120
120
Electrical data
Power consumption
[VA]
100
200
50 .. 60 Hz
AC
[V]
48, 60, 110/127, 230/250
Rated control supply
voltage Vs
DC
[V]
24, 48, 60, 110/127, 230/250
Fuse (time-lag "T"), DIAZED
[A]
4 at 48V AC, 60V AC; 2 at 110/127V, 230/250V)
2
Circuit breaker, C characteristic
[A]
4 at 48V AC, 60V AC; 2 at 110/127V, 230/250V)
2
1)
Circuit-dependent; changeover contact also permissible but note the pause times between ON and OFF.
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......