Technical data
12.6 Power loss
3VL molded-case circuit breakers
168
System Manual, 03/2009, 110 0110 - 02 DS 01
Electronic trip units (ETU / LCD-ETU)
The table below shows the power loss for electronic trip units (ETU / LCD-ETU). The power
loss applies for I
n
with 3-phase balanced load. The specified power loss is the sum of all
current paths.
The current path resistance is only a guide value and can fluctuate.
Table 12- 30 Power loss for electronic overload releases (ETU / LCD-ETU)
Type
Rated current [A]
Power loss [W]
Path resistance [mΩ]
63
7
0,59
100
16
0,53
VL160
160
40
0,52
200
42
0,35
VL250
250
60
0,32
315
60
0,2
VL400
400
90
0,19
VL630
630
160
0,13
VL800
800
250
0,13
1000
135
0,045
VL1250
1250
210
0,045
VL1600
1600
260
0,034
Starter combinations
The table below shows the power loss and the current path resistance for starter
combinations. The power loss applies for I
n
with 3-phase balanced load. The specified power
loss is the sum of all current paths. The current path resistance is only a guide value and can
fluctuate.
Table 12- 31 Power loss for starter combinations
Type
Rated current [A]
Power loss [W]
Path resistance [mΩ]
63
7
0,59
100
16
0,53
VL160
160
40
0,52
VL250
250
60
0,32
200
30
0,25
250
42
0,22
VL400
315
60
0,20
315
59
0,20
VL630
500
118
0,16
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......