Functions
5.1 Current protection
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
59
9/
/
/
/
3(
16(B
1
Figure 5-6
4-pole circuit breaker, current converter installed internally
Measurement method 2: Direct detection of the ground-fault current via a current transformer at the
grounded star point of the transformer
The current converter is installed direct at the grounded star point of the transformer.
9/
/
/
/
3(
16(B
7
1
Figure 5-7
3-pole circuit breaker, current converter at the grounded star point of the transformer