System overview
4.2 Key data
3VL molded-case circuit breakers
38
System Manual, 03/2009, 110 0110 - 02 DS 01
4.2.4
General data - motorized operating mechanisms
Type
VL160X
3VL1
VL160
3VL2
VL250
3VL3
VL400
VL4
VL630
3VL5
VL800
VL6
VL1250
3VL7
VL1600
3VL8
Motorized operating mechanism x
x
x
-
-
-
x
x
Stored-energy motorized
operating mechanism
(synchronization-enabled)
x
x
x
x
x
x
-
-
Motorized operating mechanism
Power consumption [VA / W]
< 100
< 100
< 100
-
-
-
< 250
Rated control supply voltage V
s
[50 / 60 Hz V AC]
42 / 110-127 / 220-240
-
-
-
42-48 / 60 /
110-127 / 220-250
Rated control supply voltage V
s
[V DC]
24 / 48 / 60 / 110-127 / 220
-
-
-
24 / 42-48 / 60
110-127 / 220-250
DIAZED fuse
(performance class gG,
characteristic time lag) [A]
4
2
-
-
-
4
2
Miniature circuit breaker
(C characteristic in accordance
with DIN VDE 0641)
4
2
-
-
-
4
2
Operating range [V]
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
-
-
-
0.85 to
1.1 x V
s
0.85 to
1.1 x V
s
Minimum command duration
at V
s
[ms]
50
50
50
-
-
-
50
50
Max. command duration,
connection-dependent
1)
Jog/pushbutton or continuous
command
-
-
-
Jog/pushbutton or
continuous
command
Total closing time [s]
< 1
< 1
< 1
-
-
-
< 5
< 5
Break time [s]
< 3
< 3
< 3
-
-
-
< 5
< 5
Pause between the commands
OFF and ON [s]
> 3
> 3
> 3
-
-
-
> 5
> 5
Pause between the commands
ON and OFF [s]
> 3
> 3
> 3
-
-
-
> 5
> 5
Max. permissible switching
frequency [1/h]
120
120
120
-
-
-
30
30
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......