Circuit diagrams
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
321
Table 14- 3 Motorized operating mechanism without stored energy for VL160X-VL250, without
undervoltage release
S0
OFF (to be provided by customer) S1
ON (to be provided by customer)
S2
Auto/manual selector switch
U<
Undervoltage release
-F1, -F2 Control circuit fuse
S01
Remote command (to be provided
by customer)
K1
Auxiliary contactor (to be provided
by customer)
PE
Protective grounding
Note
Automatic reset/close
A separate alarm switch contact (7-8) can be connected for automatic reset after tripping. To
prevent a fault occurring in the protected circuit, automatic closing of a tripped circuit breaker
is not recommended.
The contact of auxiliary contactor K1 or K3 prevents no-load operation of the circuit breaker
when the undervoltage release "<U" is without power. No load operations represent a high
level of stress for the circuit breaker. If the undervoltage release is without power, auxiliary
contactor K1 or K3 has not picked up. The contact in the ON circuit (control circuit) of the
motorized operating mechanism is thus not closed, that is, the circuit breaker cannot be
switched.
This auxiliary contactor is not necessary in principle if the undervoltage release is supplied
uninterrupted (e.g. pushbutton S01) from the same source as the motorized operating
mechanism itself (e.g. contact 4).
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......