Technical data
12.5 Derating factors
3VL molded-case circuit breakers
164
System Manual, 03/2009, 110 0110 - 02 DS 01
Electronic trip unit
Fixed mounting:
Table 12- 25 Derating factors for electronic trip unit (fixed mounting)
Max. rated uninterrupted current according to the
ambient temperature x I
n
Circuit
breaker
I
n
At 50 °C
[A]
Cross-
section Cu
[mm
2
]min
Cross-
section Al
[mm
2
]min
40 °C
50 °C
60 °C
70 °C
VL160
63
100
160
16
35
70
25
50
95
1
1
1
1
1
1
1
1
1
0,80
0,80
0,80
VL250
200
250
95
120
120
185
1
1
1
1
1
0,95
0,80
0,80
VL400
315
400
185
240
2x120
2x150
1
1
1
1
1
0,95
0,80
0,80
VL630
630
2x185
2x240
1
1
0,95
0,80
VL800
800
2x50x5
1
1
0,95
0,80
VL1250
1000
1250
2x60x5
2x80x5
1
1
1
1
1
0,95
0,80
0,80
VL1600
1600
2x100x5
1
1
0,95
0,80
Note
The electronic trip units with the ordering data Sx, Mx, Tx and Nx have a thermal self-
protection feature that trips the breaker if the electronics components reach 100°C.
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......