Product description
3.5 Motorized operating mechanisms (optional)
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
27
3.5.1
Stored-energy motorized operating mechanism
Motorized operating mechanism for VL160X-VL800
●
The stored-energy motorized operating mechanism is suitable for synchronization tasks.
●
The motor charges a stored-energy spring mechanism and moves the SENTRON VL
toggle handle to the "OFF/RESET" position.
●
The stored-energy spring mechanism discharges when actuated, quickly switching the
SENTRON VL toggle handle to the "ON" position.
●
A changeover switch allows local (Manual) or remote (Auto) operation to be selected.
●
The manual actuator handle is located on the front of the operating mechanism cover.
Figure 3-3
Stored-energy motorized operating mechanism
3.5.2
Motorized operating mechanism without stored-energy mechanism
Motorized operating mechanism for VL1250-1600
●
The motor drives a mechanism that switches the SENTRON VL toggle handle to the "ON"
and "OFF/RESET" positions.
●