Technical data
12.5 Derating factors
3VL molded-case circuit breakers
162
System Manual, 03/2009, 110 0110 - 02 DS 01
Thermomagnetic overcurrent trip unit + RCD module
Fixed mounting:
Table 12- 23 Derating factors for thermomagnetic overcurrent trip unit + RCD module (fixed mounting)
Max. rated uninterrupted current according to the
ambient temperature x I
n
Circuit
breaker
I
n
at 50 °C
[A]
Cross-
section Cu
[mm
2
]min
Cross-
section Al
[mm
2
]min
40 °C
50 °C
60 °C
70 °C
VL160X
16
20
25
32
40
50
63
80
100
120
160
2,5
2,5
4
6
10
10
16
25
35
50
70
4
4
6
10
10
16
25
35
50
70
95
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,80
0,80
0,80
0,80
0,80
0,80
0,80
0,80
0,80
0,80
0,80
VL160
50
63
80
100
125
160
10
16
25
35
50
70
16
25
35
50
70
95
1
1
1
1
1
1
1
1
1
1
1
1
0,93
0,93
0,93
0,93
0,93
0,93
0,80
0,80
0,80
0,80
0,80
0,80
VL250
200
250
95
120
120
185
1
1
1
1
0,86
0,86
0,80
0,80
VL400
200
250
315
400
95
120
185
240
120
185
2x120
2x150
1
1
1
1
1
1
1
1
0,86
0,86
0,86
0,86
0,80
0,80
0,80
0,80
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......