Technical data
12.8 Motorized operating mechanisms
3VL molded-case circuit breakers
172
System Manual, 03/2009, 110 0110 - 02 DS 01
Table 12- 36 Stored-energy motorized operating mechanism for VL630 and VL800 or without stored energy for VL1250 and
VL1600
Type
VL630
VL800
VL1250
VL1600
Synchronizable
X
X
--
--
Operating range
[V]
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
0,85 ... 1.1 U
S
Minimum command duration at V
S
[ms]
50
50
50
50
Max. command duration
1)
[ms]
Jog or pushbutton command
Total closing time
[ms]
<100
<100
<5000
<5000
Break time
[s]
<5
<5
<5
<5
Pause between ON and OFF command
[s]
>1
>1
>1
>1
Pause between OFF and ON command
[s]
>5
>5
>5
>5
Max. permissible switching frequency
1/h
60
60
30
30
Electrical data
Power consumption
[VA]
250
50 .. 60 Hz
AC
[V]
48, 60, 110/127, 230/250
Rated control supply
voltage Vs
DC
[V]
24, 48, 60, 110/127, 230/250
Fuse (time-lag "T"), DIAZED
[A]
4 at 48V AC, 60V AC;
2 at 110/127V, 230/250V
Circuit breaker, C characteristic
[A]
4 at 48V AC, 60V AC;
2 at 110/127V, 230/250V
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......