41
Functions
5
5.1
Current protection
5.1.1
Overcurrent trip unit
The SENTRON VL circuit breakers are designed on the principle of magnetic repulsion of
the contacts. The contacts open before the expected peak-value of the short-circuit current is
reached. Magnetic repulsion of the contacts very significantly reduces the thermal load I
2
t as
well as the mechanical load resulting from the impulse short-circuit current IP of the system
components that occur during a short-circuit.
(1)
Main connections
(2)
Breaker mechanism
(3)
Overcurrent trip unit
(4)
Movable contact arm
(5)
Arc chute
(6)
Enclosure
Figure 5-1
Interior view MCCB