![Siemens SENTRON 3VL series System Manual Download Page 32](http://html.mh-extra.com/html/siemens/sentron-3vl-series/sentron-3vl-series_system-manual_382625032.webp)
System overview
4.2 Key data
3VL molded-case circuit breakers
32
System Manual, 03/2009, 110 0110 - 02 DS 01
Type
VL160X
3VL1
VL160
3VL2
VL250
3VL3
VL400
VL4
VL630
3VL5
VL800
VL6
VL1250
3VL7
VL1600
3VL8
Round conductor terminal for cable
•
Solid or stranded cable;
copper or Al [mm²]
16 to 70 16 to 70 25 to 185 50 to 300 -
-
-
-
•
Finely stranded with end
sleeve [mm²]
16 to 50 16 to 50 25 to 120 50 to 240 -
-
-
-
Multiple feed-in terminal
8)
•
Solid or stranded cable;
copper or Al [mm²]
-
-
-
Qty. 2
50 to 120
Qty. 2
50 to 240
Qty. 3
50 to 240
Qty. 4
50 to 240
-
•
Finely stranded with end
sleeve
-
-
-
2 pieces
50 to 95
2 pieces
50 to 185
3 pieces
50 to 185
4 pieces
50 to 185
-
•
Direct connection of busbars;
Cu or Al [mm]
17 x 7
22 x 7
24 x 7
32 x 10
40 x 10
2 x 40 x
10
2 x 50 x
10
3 x 60 x
10
•
Screw for screw-type
connection
M6
M6
M8
M8
M6
M8
M8
-
Connection cross-sections for control circuits with terminal connection
Screw-type terminals
•
Solid [mm²]
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
0.75 to
1.5
•
Finely stranded with end
sleeve [mm²]
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
0.75 to
1.0
See installation instructions for details.
Summary of Contents for SENTRON 3VL series
Page 2: ......
Page 10: ...Table of contents 3VL molded case circuit breakers 10 System Manual 03 2009 110 0110 02 DS 01 ...
Page 350: ...Correction sheet 3VL molded case circuit breakers 350 System Manual 03 2009 110 0110 02 DS 01 ...
Page 358: ...Glossary 3VL molded case circuit breakers 358 System Manual 03 2009 110 0110 02 DS 01 ...
Page 359: ......