System overview
4.2 Key data
3VL molded-case circuit breakers
36
System Manual, 03/2009, 110 0110 - 02 DS 01
4.2.3
General data - Trip units
Group No. 1
VL160X to VL400
Group No. 2
VL630 to VL1600
Undervoltage release
Response voltage:
•
Drop (switch tripped) [V]
0.35 to 0.70 x U
s
0.35 to 0.70 x U
s
•
Pick-up (switch can be
switched on) [V]
0.85 to 1.1 x U
s
0.85 to 1.1 x U
s
Power consumption (continuous operation) at:
•
50 / 60 Hz 24 V AC [VA]
1.4
1.2
•
50 / 60 Hz 110 to 127 V AC
[VA]
1.5
1.1
•
50 / 60 Hz 220 to 250 V AC
[VA]
1.5
2.1
•
50 / 60 Hz 208 V AC [VA]
1.8
2.2
•
50 / 60 Hz 277 V AC [VA]
2.1
1.6
•
50 / 60 Hz 380 to 415 V AC
[VA]
1.6
2.0
•
50 / 60 Hz 440 to 480 V AC
[VA]
1.8
2.3
•
50 / 60 Hz 500 to 525 V AC
[VA]
2.5
2.9
•
50 / 60 Hz 600 V AC [VA]
2.4
--
•
12 V DC (W)
0.75
1.2
•
24 V DC (W)
0.8
1.4
•
48 V DC (W)
0.8
1.5
•
60 V DC (W)
0.8
1.6
•
110 to 127 V DC (W)
0.8
1.2
•
220 to 250 V DC (W)
0.8
1.5
Max. opening (release) time
[ms]:
50
80