Technical data
12.6 Power loss
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
169
Molded-case non-automatic circuit breakers
The table below shows the power loss and the current path resistance for molded-case non-
automatic circuit breakers. The power loss applies for I
n
with 3-phase balanced load. The
specified power loss is the sum of all current paths. The current path resistance is only a
guide value and can fluctuate.
Table 12- 32 Power loss for molded-case circuit breakers
Type
Rated current [A]
Power loss [W]
Path resistance [mΩ]
100
13
0,43
VL160X
160
34
0,44
100
16
0,53
VL160
160
40
0,52
VL250
250
60
0,32
VL400
400
90
0,19
VL630
630
160
0,13
VL800
800
250
0,13
VL1250
1250
210
0,045
VL1600
1600
260
0,034