Diagnostics
12.5 RMON
SCALANCE XM-400/XR-500 Command Line Interface (CLI)
Configuration Manual, 06/2016, C79000-G8976-C252-11
937
12.5.2.3
rmon alarm
Description
With this command, you configure an alarm for monitoring a MIB variable. The variable is
checked at specific intervals to determine whether or not it has exceeded or fallen below
threshold values. Events are assigned to these occurrences.
Requirement
You are in the Global configuration mode.
The command prompt is as follows:
cli(config)#
Syntax
Call up the command with the following parameters:
rmon alarm <alarm-number><mib-object-id(255)>
<sample-interval-time(1-65535)>
{absolute|delta}
rising-threshold<value(0-2147483647)>[risingevent-number(1-65535)]
falling-threshold<value(0-2147483647)>[fallingevent-number(1-65535)]
[owner<ownername(127)>]
The parameters have the following meaning:
Parameter
Description
Range of values / note
alarm-number
Number of the alarm
1 ... 250
mib-object-id
Name of the MIB variable
max. 255 characters
sample-interval-
time
Interval for the check [s]
1 ... 65535
absolute
The current absolute value of the moni-
tored MIB is evaluated
-
delta
The difference between the current and
the previous value of the monitored
MIB is evaluated
-
rising-threshold
Keyword for threshold value for rising
or high variable values
-
value
Relevant threshold value
0 ... 2147483647
risingevent-number
Event number for this
1 ... 65535
falling-threshold
Keyword for threshold value for falling
or low variable values
-
value
Relevant threshold value
0 ... 2147483647
fallingevent-number
Event number for this
1 ... 65535
owner
User to which the alarm is assigned
-
ownername
User name of the user
max. 127 characters