Diagnostics
12.1 Event and fault handling
SCALANCE XM-400/XR-500 Command Line Interface (CLI)
Configuration Manual, 06/2016, C79000-G8976-C252-11
901
Further notes
You enable the setting with the
severity
command.
You display the status of this function and other information
show events severity
.
12.1.6.8
power
Description
With this command, you configure and activate the monitoring of the power supplies.
Requirement
You are in the EVENTS configuration mode.
The command prompt is as follows:
cli(config-events)#
Syntax
Call up the command with the following parameters:
power [{L1|L2}]
The parameters have the following meaning:
Parameter
Description
L1
Monitoring of power supply 1
L2
Monitoring of power supply 2
If you do not select any parameters from the parameter list, the default value "L1 and L2" is
used.
Result
The setting for monitoring the power supplies is configured.
Further notes
You can display the current setting with the
show events faults config
command.
You disable the function with the
no power
command.
12.1.6.9
no power
Description
With this command, you disable the monitoring of the power supplies.