07.96
Description
3-14
6ZB5 430–0BH02–1AA0
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
Slave station has been parameterized by another master
Slave station is not an IM 328–N (parameter error)
Bit is always ”0”
Function is not supported
Device–oriented or ID–oriented diagnostics exists
The configuration data sent form the master to the slave station does not match
the structure of the slave station
Slave station is not ready for data exchange
Slave station cannot be addressed
((Bild rechts))
Must be reparameterized
Slave station cannot continue until fault is remedied
Bit is always ”1”
Response monitoring is activated
Slave station is in ”FREEZE” mod4e
Slave station is in ”SYNC” mode
Bit is always ”0”
Slave station is deactivated
Fig. 3–9 Structure of the diagnostics word after request with Code = 0
((Bild))
Code = 1 Station 3 and Master address
Without meaning Address of the master of that has parameterized the slave
station
Fig. 3–10 Structure of the diagnostics word after request with Code = 1
((S. 3–19))
Requesting manufacturer ID Code = 2
The byte ”manufacturer ID” describes the type of slave station.
Load diagnostics for Code 2 (n = station number)
and transfer the diagnostics words
Read and evaluate the diagnostics word
Code = 2 Manufacturer ID
The manufacturer ID for IM 328–N, DP slave is 8024hex
Fig. 3–11 Structure of the diagnostics word after request with code = 2
Note
The IM 328–N module (standard slave mode) and the slave interface of the IM
329–N module have the same manufacturer ID.
Requesting and reading device–oriented diagnostics Code = 3